Is there an example of using MBP_MSTR with OpCode 15 to access 3X registers over ModbusTCP?
Issue:
Is there an example of using MBP_MSTR with OpCode 15 to access 3X registers over ModbusTCP?
Product Line:
Modicon Quantum
Modicon Momentum
Modicon M580
Environment:
EcoStruxure Control Expert
Unity Pro
Resolution:
The attached project in ZEF format contains an example of how to configure the MBP_MSTR with OpCode 15 to read 3x / 300000 / %IW registers from a server Modbus TCP device.
This example was created with a double-wide Quantum CPU module, but the MBP_MSTR can be used in the same way with Momentum and M580 CPU modules.
In the Data Editor, you will find the Control and Data Arrays. Read the comments section for each of the registers to see how they need to be configured.
Is there an example of using MBP_MSTR with OpCode 15 to access 3X registers over ModbusTCP?
Product Line:
Modicon Quantum
Modicon Momentum
Modicon M580
Environment:
EcoStruxure Control Expert
Unity Pro
Resolution:
The attached project in ZEF format contains an example of how to configure the MBP_MSTR with OpCode 15 to read 3x / 300000 / %IW registers from a server Modbus TCP device.
This example was created with a double-wide Quantum CPU module, but the MBP_MSTR can be used in the same way with Momentum and M580 CPU modules.
In the Data Editor, you will find the Control and Data Arrays. Read the comments section for each of the registers to see how they need to be configured.
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.