What does an OBF fault mean on an ATV12 drive?

Article available in these languages:

  • Španělština

Resolution:
The OBF (Over Braking Fault) occurs when the drive detects excessive braking energy, typically caused by rapid deceleration or high load inertia.

Possible causes are:

  • Deceleration time is too short
  • High inertia load (motor or driven machine)
  • Input line voltage too high
  • Voltage spikes or surges in the power supply

To mitigate the issues:

  • Increase the deceleration time (DEC) to reduce braking stress
  • Install a braking resistor or braking module if required
  • Verify the line supply voltage is within limits- Must not exceed +20% of the rated voltage during operation
  • Check for voltage fluctuations, spikes, or unstable power conditions

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie