Cannot Open EPZ Relay Configuration File in eSetup Easergy Pro
Issue
A relay EPZ configuration file cannot be opened in eSetup Easergy Pro, even when using the latest available version (at this time v4.11.2). A warning message appears when attempting to open the file.
Product
- eSetup Easergy Pro Software
- Supported Powerlogic relays
Environment
- eSetup Easergy Pro v4.11.2
- Windows PC
- Local relay configuration files
- Software configured with custom or default file paths
Cause
eSetup Easergy Pro was not configured to point to the correct Template (configuration) folder. Specifically, the Template folder under General > Files & Folders was not set to the Configs directory where relay configuration files are stored. As a result, the software could not locate or open the configuration files, even though they were valid.
Resolution
The software configuration needs to be reviewed and corrected. To resolve the issue:
- Open eSetup Easergy Pro.
- Go to General > Files & Folders.
- Set the Template folder to point to the Configs directory (according to the local installation path).
- Apply the changes and retry opening the relay configuration file.
After updating the Template folder path to the correct Configs directory, you will be able to successfully open the EPZ relay configuration files.
Please check the next screenshoot:
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.