What is the heat/power dissipation on the LRD range of overloads?
Please see the table below for heat/power dissipation on the LRD range of overload relays. For heat dissipation on the LRD overload relays with Everlink terminals, please see FAQ000233560.
Reference | Setting range (A) | Power dissipated in |
| | VA at Ith max. |
LRD01 | 0.1-0.16 | 1.33 |
LRD02 | 0.16-0.25 | 1.4 |
LRD03 | 0.25-0.40 | 1.38 |
LRD04 | 0.40-0.63 | 1.24 |
LRD05 | 0.63-1 | 1.55 |
LRD06 | 1-1.6 | 1.61 |
LRD07 | 1.6-2.5 | 1.67 |
LRD08 | 2.5-4 | 1.61 |
LRD10 | 4-6 | 2.14 |
LRD12 | 5.5-8 | 1.83 |
LRD14 | 7-10 | 1.77 |
LRD16 | 9-13 | 2.42 |
LRD21 | 12-18 | 1.99 |
LRD22 | 16-24 | 2.53 |
LRD32 | 23-32 | 2.43 |
LRD35 | 30-38 | 3.04 |
LRD3322 | 17-25 | 3.42 |
LRD3353 | 23-32 | 3.81 |
LRD3355 | 30-40 | 4.52 |
LRD3357 | 37-50 | 6 |
LRD3359 | 48-65 | 7.98 |
LRD3361 | 55-70 | 8.18 |
LRD3363 | 63-80 | 10.17 |
LRD3365 | 80-104 | 5.62 |
LRD4365 | 80-104 | 6.7 |
LRD4367 | 95-120 | 8.35 |
LRD4369 | 110-140 | 10.38 |
LRD33656 | 80-104 | 7.57 |
LRD33676 | 95-120 | 9.5 |
LRD33696 | 110-140 | 11.95 |