Veelgestelde vragen (FAQ's) zoeken
What is the operating temperature range of the ATS01 soft starters?
Issue:
What is ATS01 soft starter operating temperature?
Product Line:
ATS01
Environment:
All series
Causes:
N/A
Resolution:
The ATS01 soft starters are rated for use in ambient temperatures ranging from -10C (14F) to +40C (104F). The starter can be used up to 50C (122F) by derating the current by 2% per degree C above 40C.
The obsolete ATS01N2**LY were rated for use in ambient temperatures ranging from 0C (32F) to +55C (131F).
What is ATS01 soft starter operating temperature?
Product Line:
ATS01
Environment:
All series
Causes:
N/A
Resolution:
The ATS01 soft starters are rated for use in ambient temperatures ranging from -10C (14F) to +40C (104F). The starter can be used up to 50C (122F) by derating the current by 2% per degree C above 40C.
The obsolete ATS01N2**LY were rated for use in ambient temperatures ranging from 0C (32F) to +55C (131F).
Gepubliceerd voor:Schneider Electric Netherlands
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie