Veelgestelde vragen (FAQ's) zoeken
ATV630 Why am I getting Motor Short circuit fault when switching STOA or STOB with an external power supply?
Issue:
ATV630 -getting Motor Short circuit fault when switching STOA or STOB, with an external power supply.
Product Line:
ATV630 process drive.
Environment:
All models and serial numbers with firmware revision below 1.3IE07
Cause:
Firmware issue.
Resolution:
This situation was verified as a problem with the drive firmware and was repaired with firmware release V1.3IE07. If you have a 630 process drive with firmware below V1.3IE07, upgrading the firmware will correct this problem.
ATV630 -getting Motor Short circuit fault when switching STOA or STOB, with an external power supply.
Product Line:
ATV630 process drive.
Environment:
All models and serial numbers with firmware revision below 1.3IE07
Cause:
Firmware issue.
Resolution:
This situation was verified as a problem with the drive firmware and was repaired with firmware release V1.3IE07. If you have a 630 process drive with firmware below V1.3IE07, upgrading the firmware will correct this problem.
Gepubliceerd voor:Schneider Electric Netherlands
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie