Where can we find the Type-2 coordination chart for ATS22?

Article available in these languages: Czech

Type 2 coordination is not possible with ATS22 due to the  soft starter internal design of power semiconductor & its internal  by-pass . Only table for coordination type 1 is available in the catalog. Attached pdf pages for type 1 coordination .