Can you switch between 2 wire control and 3 wire control using a logic input?
Issue:
Change between 2 wire control and 3 wire control with logic input.
Product Line:
Altivar 61, ATV61
Environment:
All models, All serial numbers.
Cause:
none
Resolution:
The drive must be programmed as either 2 wire or 3 wire control. There is no way to change this without both programming and wiring changes to the drive.
2 wire control - LI1 is run forward. The default programming is a transition of LI1 from low to high in order to run. This can be changed to Level switching. LI1 must stay closed for the drive to run.
3 wire control - LI1 is stop (NC contact) and LI2 is run forward. A momentary or maintained closure of LI2 causes the drive to run forward. LI1 (stop) needs to be opened in order to stop the drive.
Change between 2 wire control and 3 wire control with logic input.
Product Line:
Altivar 61, ATV61
Environment:
All models, All serial numbers.
Cause:
none
Resolution:
The drive must be programmed as either 2 wire or 3 wire control. There is no way to change this without both programming and wiring changes to the drive.
2 wire control - LI1 is run forward. The default programming is a transition of LI1 from low to high in order to run. This can be changed to Level switching. LI1 must stay closed for the drive to run.
3 wire control - LI1 is stop (NC contact) and LI2 is run forward. A momentary or maintained closure of LI2 causes the drive to run forward. LI1 (stop) needs to be opened in order to stop the drive.
Publicerad för: Schneider Electric Sverige
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.