Hur kan vi hjälpa dig idag?

Will the ATV61 or ATV71 drives 4 to 20 ma input speed signal control the drive motor speed between LSP to HSP or 0 to 60hz?

Issue:
ATV61 or ATV71uses 4-20mA input speed signal to control the motor speed between LSP to HSP.

Product Line:
Altivar ATV61

Environment:
All

Cause:
They have low speed LSP set to 45 hz but they want the drives analog input to allow the drive to run between 0 to 60hz not low speed to high speed.

Resolution:
The Drive wills analog inputs will allow the drive to run between Low speed to high speed.   If you want to have a low speed setting above 0 and still want the drive to follow 0 to 60hz then set the Reference Template Parameter (BSP)  in Menu 1.5  to Pedestal mode.

Menu 1.5 programming below.


pedestal


Schneider Electric Sverige

Utforska mer

Produktfamilj

Utforska mer

Produktfamilj

Behöver du hjälp?

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.