Why do I get this validation error in Vijeo Designer 6.2 - The folder C:\Projects\......\Vijeo Configs does not exist. Please enter a valid folder.

You will get this error when the Vijeo Designer project contains an image file reference or a browser page reference that was build on one computer and exported to another computer but the referenced file path was not created on the second computer. Vijeo Designer must see the configured path to the referenced files on the computer you are building the project.

Solution: Create the path reported in the error message and build the project again.