VIDEO: Testing Citect Credentials Fail for Application Services Host

Issue
A users credentials fail to authenticate in Application Configuration Utility > Application Services Host:
image
Citect connection unavailable.
Note: Citect runtime must be running to perform this test

Note: Citect Runtime is already running.


Product Line
PowerSCADA Expert 8.1, 8.2, 9.0 (PSE 8.x, 9.x)

Environment
Application Configuration Utility

Cause
A successful connection by the Schneider Electric ApplicationServiceHost service requires a user already defined in the PowerSCADA project, server IP address and a parameter in the INI file.  However, testing citect credentials will not work if it's running as a service. In this resolution, the INI parameter is missing.


Resolution
1.  In Citect INI file, set [ctAPI] Remote = 1.

image


2.  Shutdown and restart the Runtime (project).

3.  Now the test will succeed:
image

**Embed video here**

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj
  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings