ATV61 and ATV71 basic integrated modbus setup assistance?
Issue:
Need ATV61 and ATV71 basic integrated modbus setup assistance.
Product Line:
ATV61 and ATV71 standard internal modbus
Environment:
All
Cause:
Basic modbus setup assistance.
Resolution:
Programming: Menu 1.9
Modbus Network
Add- address set to 1 to 247
tbr= modbus baud rate choose 4.8, 9.6, 19.2 or 38.4K
tFO=Modbus format choose 8O1, 8E1, 8N1 or 8N2
ttO= modbus timeout set between 0.1 to 30 seconds.
You must now power cycle the drive and wait until the display goes out and then you can power it back up again after you change any of the modbus settings.
Wiring is pins 4 and 5 for data + and - and pin 8 for com
The wiring connection is a RJ45
Need ATV61 and ATV71 basic integrated modbus setup assistance.
Product Line:
ATV61 and ATV71 standard internal modbus
Environment:
All
Cause:
Basic modbus setup assistance.
Resolution:
Programming: Menu 1.9
Modbus Network
Add- address set to 1 to 247
tbr= modbus baud rate choose 4.8, 9.6, 19.2 or 38.4K
tFO=Modbus format choose 8O1, 8E1, 8N1 or 8N2
ttO= modbus timeout set between 0.1 to 30 seconds.
You must now power cycle the drive and wait until the display goes out and then you can power it back up again after you change any of the modbus settings.
Wiring is pins 4 and 5 for data + and - and pin 8 for com
The wiring connection is a RJ45
Publicerad för: Schneider Electric Sverige


Behöver du hjälp?
Produktväljare
Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.
Begär en offert
Ställ din fråga online så kontaktar vi dig.
Här köper du
Hitta enkelt närmaste Schneider Electric-distributör på din ort.
Hjälpcenter
Hitta alla supportresurser som du behöver på ett ställe.