How to read data from MX EcoDrive frequency converter over Modbus RTU?

MX drives are totally different than Altivar drives. See modbus manual for MX eco drives in the attachment. Page 6 shows all important information and page 16 example with function code 17. If you want only to read parameters from MX eco, (not sending commands), then use function code 3 - read holding registers

The modus request will look: (each byte separated by "-")
Slave address - 16#03 - 16#00 - 16#FA - 16#00 - 16#02 - CRCLow - CRCHi

16#00FA is the address of the status word ZTW and 16#0002 means that 2 words will be read:
ZTW (status word) from address 16#00FA
Fact (actual frequency) from address 16#00FB

If you need to read more data, use another request.
Full request and response with function code 3 shown on page 32

Schneider Electric Sverige

Bilagor
8_P01_034_EN_00-00b.pdf [1.55 MB]
Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings