How to monitor the SCADAPack x70 time using Modbus.

  • Under the Configuration -SPx70 Controller in RemoteConnect select the object tab.
  • To add the Hour, Minutes and Seconds in the RemoteConnect Object.
  • In Object  Configuration, click add object and enter the following information below when monitoring the HOUR.
  • Assigning modbus register for the HOUR by selecting the modbus tab.
  • click add object and enter the following information below when monitoring the MINUTE.
  • Assigning modbus register for MINUTE by selecting the modbus tab.
  • click add object and enter the following information below when monitoring the SECOND.
  • Assigning modbus register for SECOND by selecting the modbus tab.
  • Hit Apply button then Write the program into the SCADAPackx70 to make changes.
  • Monitor the modbus registers assigned. In this example monitor register 40100 for HOUR, 40101 for MINUTE and 40102 for SECOND.


Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings