Operator Terminal Expert- In the Alarm Summary object, how to configure the alarm messages to not be displayed when alarm is returned (OFF).

Issue:
In the Alarm Summary object, how to configure the alarm messages to not be displayed when alarm is returned (OFF).

Product Line:
EcoStruxure Operator Terminal Expert (all versions)

Resolution:
In Operator Terminal Expert, to not have the alarm messages displayed in the Alarm Summary object when returned (OFF):

When using the Alarm Mode "Active", the ExceptRTN property must be selected.

Screenshot of property to select.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.