How to change the MAST task Cyclic to Periodic in RemoteConnect and SCADAPack x70 device?

In Cyclic mode, the MAST task uses all available time. Sufficient time should be allowed for bursts of other activity on the SCADAPack x70 device. For this reason, Cyclic mode is not recommended.

To change MAST task from Cyclic to Periodic:
  • Open RemoteConnect software
  • Create new project for SCADAPack 474
  • In Configuration-SPx70 Controller>SCADAPack x70 logic, open SCADAPack x70 logic editor
  • Under Project>Programs>Tasks>MAST, right click on MAST and select properties
  • MAST's properties window should appear
  • Change the configuration from Cyclic to Periodic, then click the Apply button and then the OK button to save the changes.
Mast
  • Make sure to apply update and build logic after writing the logic program

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings