ViewX Closes on Startup following an Upgrade

There have been reports of ViewX closing right after being opened.  (These instances occurred following a Geo SCADA upgrade – I.E. upgrading from GS 2019 to GS 2023.)  In those instances, the issue was due to the creation of duplicate files in a different Windows folder.  The steps to remedy this are listed below.

Launch Windows File Explorer and look at the following two folders:

C:\Program Files (x86)\Schneider Electric\ClearSCADA

and

C:\Program Files (x86)\Schneider Electric\ClearSCADA\Modules

The CEFSharp*.* files (see images below) should only be found in the 'Modules' folder.

If any CEFSharp*.* files are found in the 'ClearSCADA' folder, these files should be deleted (from the ‘ClearSCADA’ folder only).  Once the files are removed from the ‘ClearSCADA’ folder, ViewX should open without issue.'

image1

image2

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

  • Produktväljare

    Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

  • Begär en offert

    Ställ din fråga online så kontaktar vi dig.

  • Här köper du

    Hitta enkelt närmaste Schneider Electric-distributör på din ort.

  • Hjälpcenter

    Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings