How to display DNP3 and/or Modbus protocol addresses in Logic Editor?

If you added DNP3 point numbers and/or Modbus register addresses before selecting the Object Protocol Address(es) in the Logic Editor custom field, you can display those addresses in the SCADAPack x70 Logic Editor:

  1. Go offline in RemoteConnect.
  2. Under My Network, right-click on SCADAPack x70 Controller Settings-DeviceDTM and select Additional Functions>Project Settings.

Display1

  1. Select the Object Protocol Address(es) in Logic Editor Custom Field checkbox.

Display2

  1. Click Ok.
  2. A window will pop up " The Project Settings have been updated. Click the View log File button to see the complete list of changes". and select Close button.

Display3

  1. Open Logic Editor
  2. Under Project > Variables & FB Instances, double click on Derived Variables and view Custom field.

Display4

Schneider Electric Sverige

Utforska mer
Produktfamilj
Utforska mer
Produktfamilj

Behöver du hjälp?

Behöver du hjälp?

Produktväljare

Produktväljare

Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

Begär en offert

Begär en offert

Ställ din fråga online så kontaktar vi dig.

Här köper du

Här köper du

Hitta enkelt närmaste Schneider Electric-distributör på din ort.

Hjälpcenter

Hjälpcenter

Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Schneider Electrics community
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings