Issue:
P24 vdc signal from one ATV212 drive to start another ATV212 drive
Product Line:
Altivar ATV212
Environment:
All
Cause:
Needs to use only one power signal to start two drives.
Resolution:
Yes. Jumper together a CC terminal from both drives so that they both have the same ground reference.
Note: The P24 power supply is limited to 200mA. Each logic input consumes about 5mA.