Naše značky

Impact-Company-Logo-English Black-01-177x54

Vitajte na webovej lokalite spoločnosti Schneider Electric

Vitajte na našej webstránke.

Prehľadávať FAQ

What is a USF fault on ATV320

Article available in these languages: thajčina

Issue:
USF fault on ATV320

Product Line:
Altivar Machine, ATV320

Environment:
All serial numbers

Cause:
• Supply mains too low
• Transient voltage dip

Resolution:
• Measure incoming line to line voltages
• Check the DC bus voltage on PA and PC
• Check the voltage and the parameters of [UNDERVOLTAGE MGT] (USb-)


ATV320 programming manual:
https://www.se.com/ww/en/download/document/NVE41295/ ​​​​​​​

Schneider Electric Slovakia

Príloha(-y)

ATV320_Programming_Manual_EN_NVE41295_03.pdfATV320_Programming_Manual_EN_NVE41295_03.pdf [2.5 MB]