Which Sepam firmware versions are compatible with the ACE850 module and support the IEC 61850 protocol?
Sepam and ACE850. What are the Sepam compatible with ACE850 and IEC 61550 Protocole ?
The Sepam that are compatible with ACE850 Accessory are :
(Sepam 20 can not support the ACE850 module)
Sepam 40 with Version >= V7.00 and S/N >= 09500001
Sepam 60 with Version Base >= V7.20 and Appli >= V7.10
Sepam 80 with Version >= V6.01 and Appli >= V6.02
If you require this functionality in the above firmware, please contact your local support center to obtain the latest firmware version.