What does an OBF fault mean on an ATV12 drive?
Resolution:
The OBF (Over Braking Fault) occurs when the drive detects excessive braking energy, typically caused by rapid deceleration or high load inertia.
Possible causes are:
- Deceleration time is too short
- High inertia load (motor or driven machine)
- Input line voltage too high
- Voltage spikes or surges in the power supply
To mitigate the issues:
- Increase the deceleration time (DEC) to reduce braking stress
- Install a braking resistor or braking module if required
- Verify the line supply voltage is within limits- Must not exceed +20% of the rated voltage during operation
- Check for voltage fluctuations, spikes, or unstable power conditions
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Опубліковано для: Schneider Electric Україна
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.