Video: How do you wire and program an ATV31 or ATV312 to follow an external 0-10vdc speed pot on Analog Input 1 and use the logic inputs for starting and stopping?
Issue:
ATV31/312 set up to follow an external 0-10vdc speed pot on AI1 and use the logic inputs for starting and stopping.
Product Line:
Altivar 31 and 312
Environment:
All models in range.
Cause:
Pot for speed control or 0-10v logic input for speed control.
Resolution:
Wiring:
Wire your external pot to AI1 com and +10vdc. (wiper wire on AI1)
Wire your Start forward command between LI1 and +24vdc.
Programming:
Step 1: Go into the CTL menu enter
Step 2: Set Fr1 to AI1
ATV31/312 set up to follow an external 0-10vdc speed pot on AI1 and use the logic inputs for starting and stopping.
Product Line:
Altivar 31 and 312
Environment:
All models in range.
Cause:
Pot for speed control or 0-10v logic input for speed control.
Resolution:
Wiring:
Wire your external pot to AI1 com and +10vdc. (wiper wire on AI1)
Wire your Start forward command between LI1 and +24vdc.
Programming:
Step 1: Go into the CTL menu enter
Step 2: Set Fr1 to AI1
Опубліковано для: Schneider Electric Україна
Вкладення
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.