Чим ми можемо вам допомогти сьогодні?
Directional protection of 2 transformers in parallel: suggested alternative settings to avoid incorrect operation (i.e. spurious tripping) of Sepam units
Goals and Symptoms
Standard setting of angle for directional protection is in this case is 45° but incorrect operation ( (i.e. spurious tripping) can occur with this setting.
Facts and Changes
Key Words and Phrases:
unexpected trips, directional detection, undetected events, non-detection, unwarranted tripping
Causes and Fixes
Attached document explains which alternative settings can be used to avoid spurious tripping.
AEDL3
-
Last Revised: 13 June 2008 by DRMApplies To: Operation of Sepam Protection Relays
Original Author: DM
Public
All content © 1992-2008 Schneider Electric
Legacy KB System (APS) Data: RESL191288 V2.0, Originally authored by KBAdPM on 02/27/2008, Last Edited by DaMi on 06/14/2008
Related ranges: Sepam series 80, Sepam series 40, Protection plan
Опубліковано для: Schneider Electric Україна
Вкладення
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.