Goals and Symptoms

How to update multiple loadables in ProWORX NxT

Facts and Changes

All versions of ProWORX NxT

Causes and Fixes

'ProWORX NxT' does not allow the update of multiple loadables at the same time. If more than 1
loadable needs to be updated, the update must be performed one at a time.

The following example updates the ESI loadable which also includes the NSUP loadable.

  • Open the project.
  • Click on 'Configuration' from the top menu bar and select 'Configuration'.
Configuration
  • Click on 'User Loadables'
  • Click on first loadable to be updated (i.e., NSUP) in the Loadables in database window.
  • Click on the Update button.


Controller configuration
  • Find the the executable file (i.e., NSUP.exe) and select it.
  • Click on the OK to close the Select Loadable File window.
Loadable file selection
  • Click on the OK in the 'Update Successful' message box.
Ok window
  • Click on the OK to save the changes and to close the Controller Configuration window.
  • Repeat the process to update the next loadable. (i.e., ESI)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings