Can the ATV600 and ATV900 Process Drive run multiple motors ?

Article available in these languages: Spanish

Issuse:
Running multiple motors with an ATV600 and ATV900.

Product Line:
ATV600 ATV900 Altivar Process Drive

Environment:
All

Cause:
To simplify application

Resolution:
Yes, you can run multiple motors on a single drive.  Each motor will need separate external overload protections.
Both motors will share the same operations,  the start/stop and speed reference controls.
The heavy duty version of the drive should be sized according to the sum of both the horsepower and full load amps of both motors.