What is the difference between Retain and Persistent variables in SoMachine V4.3?

Issue:

What is the difference between Retain and Persistent variables in SoMachine V4.3?

Product Line:

SoMachine V4.3

Resolution:

1: Retain variables will be reinitialized after: reset cold, reset origin and application download otherwise the values are maintained;

2: Persistent variables will be reinitialized after Reset origin only;

Note: Persistent and Persistent Retain are the same (different wording comes from prior versions of CoDeSys);

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.