Чим ми можемо вам допомогти сьогодні?

Is it possible to change application type of my Sepam?

Issue
A new protection application type is need for the existing Sepam.

Product Line
Sepam series 20
Sepam series 40
Sepam series 80

Environment
Application Type

Resolution
The answer is a little bit different according to the Sepam series:

  • ​Sepam series 20 and 40: Modification of Sepam application type requires replacement of your complete Sepam. You need to order a new PowerLogic Protection Relay with the correct application type needed.
  • Sepam series 60 and 80: As application type is in the cartridge, modification of Sepam application type requires only replacement of the cartridge. You need to order a new cartridge with the application type needed. Note: be careful, since you may need to purchase additional CCA63x CT adapters, depending on which Application Types are involved.

Note that in all cases, a firmware patch cannot modify application type of a Sepam.

Update Note (April 2026).

The Sepam 20/40 range is obsolete and has been replaced by the PowerLogic P3 / P5 line, depending on the application. Likewise, the Sepam 60/80 range is in the final stage of its commercial life, and for new projects it can be replaced by the PowerLogic P7.

Schneider Electric Україна

Досліджуйте більше

Досліджуйте більше

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.