Issue:
Start an ATV312 using Modbus
Product Line:
Variable Frequency Drives
Environment:
Applies to ATV312
Cause:
Customer is not able to start the drive using Modbus.
Resolution:
Suggested to follow the status chart and send the values to the command word in sequence Hex 6 then 7 then F to Address 8501 (assuming there is no offset)
Start an ATV312 using Modbus
Product Line:
Variable Frequency Drives
Environment:
Applies to ATV312
Cause:
Customer is not able to start the drive using Modbus.
Resolution:
Suggested to follow the status chart and send the values to the command word in sequence Hex 6 then 7 then F to Address 8501 (assuming there is no offset)
Опубліковано для: Schneider Electric Україна

