Index issue due after conversion from Modsfoft, Proworx or Concept application in Unity Pro.
In Unity pro Index can be :
Example :
SortInterfaceOut.SortLQuantity := Decode_Pallet_Pattern[Scanner_Info[8].PIF.Pattern].CasesPerPallet;
is converted to this code by Unity pro : SortInterfaceOut.SortLQuantity := Decode_Pallet_Pattern[Scanner_InfoDecode_Pallet_PatternsPerPallet;
In order to avoid this, just affect in a temporary variable the value of "Scanner_Info[8].PIF.Pattern" :
Temp_Int := Scanner_Info[8].PIF.Pattern;
SortInterfaceOut.SortLQuantity := Decode_Pallet_Pattern[Temp_Int].CasesPerPallet;
- a value belonging to an Integer type
- an arithmetical expression made up of Integer types
Example :
SortInterfaceOut.SortLQuantity := Decode_Pallet_Pattern[Scanner_Info[8].PIF.Pattern].CasesPerPallet;
is converted to this code by Unity pro : SortInterfaceOut.SortLQuantity := Decode_Pallet_Pattern[Scanner_InfoDecode_Pallet_PatternsPerPallet;
In order to avoid this, just affect in a temporary variable the value of "Scanner_Info[8].PIF.Pattern" :
Temp_Int := Scanner_Info[8].PIF.Pattern;
SortInterfaceOut.SortLQuantity := Decode_Pallet_Pattern[Temp_Int].CasesPerPallet;
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.