Is it possible to increase the lifespan of the Magelis / Harmony HMI screen by turning down the brightness?
Issue:
Is it possible to increase the lifespan of the Magelis / Harmony HMI screen by turning down the brightness?
Product Line:
XBTGC/GK/GT, HMIGTO/GTU/STO/STU, Box PC, Panel PC, Magelis, HMI, life cycle
Resolution:
When current applied the backlight is decreased, lifetime will be extended. However, power is always provided to the LCD panel, even if LCD entering Standby and Sleep mode. Therefore, there is no way to extend the lifetime of the screen.
Is it possible to increase the lifespan of the Magelis / Harmony HMI screen by turning down the brightness?
Product Line:
XBTGC/GK/GT, HMIGTO/GTU/STO/STU, Box PC, Panel PC, Magelis, HMI, life cycle
Resolution:
When current applied the backlight is decreased, lifetime will be extended. However, power is always provided to the LCD panel, even if LCD entering Standby and Sleep mode. Therefore, there is no way to extend the lifetime of the screen.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.