MiCOM relays. Do I need to use the password to read/ write information via modbus protocol?
MiCOM Px2 - there is no need to use any password for modbus communication
MiCOM Px3 - there is no need to use any password for modbus communication
MiCOM Px4 - there is no need to use any password for modbus communication in the most part of the firmwares
Exceptions are:
In the mentioned above firmwares some read/write commands should be preceded by the level 3 password. The default one is "AAAA" or "AAAA " (41 41 41 41 or 41 41 41 41 20 20 20 20 in hexa).
MiCOM Px3 - there is no need to use any password for modbus communication
MiCOM Px4 - there is no need to use any password for modbus communication in the most part of the firmwares
Exceptions are:
| Range | Major Firmware Version |
| P14x | 46, A0, B0B |
| P24x | D0 |
| P34x | B0, E0, B1, E1 |
| P44x | C7, E0 |
| P44y | D0, F0, D1, F1, D2, F2 |
| P54x | D0, D1, D2 |
| P64x | 03, B1 |
| P74x | B0 |
| P746 | B2, C2 |
| P841 | C0, D0, C1, D1, C2, D2 |
| P849 | B0 |
In the mentioned above firmwares some read/write commands should be preceded by the level 3 password. The default one is "AAAA" or "AAAA " (41 41 41 41 or 41 41 41 41 20 20 20 20 in hexa).
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.