Video: How do I check communication between my Premium PLC TER port and the Uni-Telway driver?

Article available in these languages:

  • Japanese

To check communication the Modicon Premium PLC and the Unitelway driver do the following:
1. Launch the Driver Manager. You can locate the driver manager icon in the control panel or from the communication drivers directory under Schneider Electric.
2. select the XWAY text tab.
3. Ensure the following:
driver name= Unitelway
driver instance= 1
remote address= 0.254.0
4. press the "connect" button and the "start" button should highlight
5. Press the start button and you should see the request count incrementing. If the request count increment, you have good communication and if it does not there is a problem with either the driver configuration or you serial port.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings