How to share data between M221 PLCs?
To share data between M221 PLCs, the READ_VAR and WRITE_VAR communication functions can be used.
Before applying these functions,
It is important to select the object type for reading or writing discrete inputs, coils, input registers and holding registers.
After the object type is selected,
Please be noted that these communication functions only work when there is rising edge signal send to the execute input.
Before applying these functions,
- Go to the configuration tab and create a remote server from Modbus TCP selection by setting up IP addresses.
It is important to select the object type for reading or writing discrete inputs, coils, input registers and holding registers.
After the object type is selected,
- Choose the first object and quantity for the real addresses. For example, if we choose object type as 'read holding registers' the first object as 0 and quantity as 2, then we selected %MW0 and %MW1 to share data between the M221 PLCs.
Please be noted that these communication functions only work when there is rising edge signal send to the execute input.
Опубліковано для: Schneider Electric Україна
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.