Issue:
ATV61/71 set up for 3 wire control.
Product Line:
Altivar 61
Altivar 71
Environment:
All
Resolution:
LI1 as stop with NC momentary contact
LI2 as start with NO momentary contact
For programming, go into drive menu, inputs and outputs menu, and set 2/3 wire control to 3 wire.
You will have to hold enter for 3 seconds for the change to go into effect.
U
ATV61/71 set up for 3 wire control.
Product Line:
Altivar 61
Altivar 71
Environment:
All
Resolution:
LI1 as stop with NC momentary contact
LI2 as start with NO momentary contact
For programming, go into drive menu, inputs and outputs menu, and set 2/3 wire control to 3 wire.
You will have to hold enter for 3 seconds for the change to go into effect.
U
Опубліковано для:Schneider Electric Україна



