Differences between ATV12 and ATV312 from Modbus point of view
Differences between ATV12 and ATV312 in Modbus communication.
The most difference between ATV12 and 312 is the state machine ETA(#3201).
ATV12 State machine: ETA(#3201)=[16#**50] -> [16#**31] -> [16#**33] -> [16#**37]
ATV312 State machine: ETA(#3201)=[16#**40] -> [16#**21] -> [16#**23] -> [16#**27]
The ETA(#3201) status shows different value between ATV12 and ATV312, You can find more detail description in corresponding manuals..
Besides this difference, the hardware and software is almost the same Modbus protocol and the address is also the same.
The most difference between ATV12 and 312 is the state machine ETA(#3201).
ATV12 State machine: ETA(#3201)=[16#**50] -> [16#**31] -> [16#**33] -> [16#**37]
ATV312 State machine: ETA(#3201)=[16#**40] -> [16#**21] -> [16#**23] -> [16#**27]
The ETA(#3201) status shows different value between ATV12 and ATV312, You can find more detail description in corresponding manuals..
Besides this difference, the hardware and software is almost the same Modbus protocol and the address is also the same.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.