Can the NetShelter CX fans be turned on/off, or fan speed raised/lowered, remotely?
Issue:
A customer asks if the Net Shelter CX fans can be controlled remotely.

Product Line:
NetShelter CX

Environment:
All models, all serial numbers.

Cause:
For various reasons the customer may want to reduce fan speed, or turn them on/off.

Resolution:

Using either NetBotz or a Switched Rack PDU you can control a specific port on the NetBotz or PDU. A temperature sensor can also be used to set thresholds for alarms, or to turn outlets on/off. Please contact your APC Representative to design a solution that suits your particular needs.

NetShelter CX fan speed cannot be raised or lowered remotely, but the AR40xxA and AR40xxIA (and all X-options) have a fan booster switch on the rear. This booster switch allows the customer to increase the standard fan speed.

Schneider Electric Україна

Can the NetShelter CX fans be turned on/off, or fan speed raised/lowered, remotely?
Issue: 
A customer asks if the Net Shelter CX fans can be controlled remotely. 

Product Line: 
NetShelter CX

Environment: 
All models, all serial numbers. 

Cause: 
For various reasons the customer may want to reduce fan speed, or turn them on/off. 

Resolution: 

Using either NetBotz or a Switched Rack PDU you can control a specific port on the NetBotz or PDU. A temperature sensor can also be used to set thresholds for alarms, or to turn outlets on/off. Please contact your APC Representative to design a solution that suits your particular needs. 

NetShelter CX fan speed cannot be raised or lowered remotely, but the AR40xxA and AR40xxIA (and all X-options) have a fan booster switch on the rear. This booster switch allows the customer to increase the standard fan speed. 
  

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.