TeSys Contactor Selection table for DC current switching?
Guide for selection of contactor for DC application is in Attachment1.
These ratings are NOT UL listed
E.g. for switching of 35A at 220VDC in utilization category DC-1 to DC-5 can be used contactor LC1D32 with 3 poles connected in series.
Опубліковано для: Schneider Electric Україна





