Issue
Configuration Manager Tool v9 fails with below errors while Read from System’ in PME v9 machine.
||Warning||None||||Could not find manifest file: D:\1.PME 9.0 Configuration Management Tool\bin\MasterFileLists\PowerMonitoringExpert\9.0\DataCenter\en\config.csv||None
||Warning||None||||Could not find manifest file: D:\1.PME 9.0 Configuration Management Tool\bin\MasterFileLists\PowerMonitoringExpert\9.0\Healthcare\en\config.csv||None

Environment
Power Monitoring Expert v9.0 system read by Configuration Manager Tool v9.
Cause
When older PME versions are upgraded in-place this registry will remain and when cause this issue when old systems are DataCenter or Healthcare. From PME 9 onwards we don’t have any such PME versions anymore.
Resolution
Open RegEdit and go to the path > “HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Schneider Electric\Power Monitoring Expert\9.0” and delete key "SolutionBuild" which contains value either 'DataCenter' or ' Healthcare'.
Configuration Manager Tool v9 fails with below errors while Read from System’ in PME v9 machine.
||Warning||None||||Could not find manifest file: D:\1.PME 9.0 Configuration Management Tool\bin\MasterFileLists\PowerMonitoringExpert\9.0\DataCenter\en\config.csv||None
||Warning||None||||Could not find manifest file: D:\1.PME 9.0 Configuration Management Tool\bin\MasterFileLists\PowerMonitoringExpert\9.0\Healthcare\en\config.csv||None
Environment
Power Monitoring Expert v9.0 system read by Configuration Manager Tool v9.
Cause
When older PME versions are upgraded in-place this registry will remain and when cause this issue when old systems are DataCenter or Healthcare. From PME 9 onwards we don’t have any such PME versions anymore.
Resolution
Open RegEdit and go to the path > “HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Schneider Electric\Power Monitoring Expert\9.0” and delete key "SolutionBuild" which contains value either 'DataCenter' or ' Healthcare'.
Опубліковано для:Schneider Electric Україна

