Slow performance of HMIBMU* Win 10 LTSC 1809.
The HMIBMU becomes very slow. Each action takes a long time to be executed (variables refresh, panel change, etc.)
The article is applicable to HMIBMU*I29D*10*, HMIBMU*I29D*E0* Win 10 LTSC 1809
See below the serial numbers
Intel graphic driver 20.19.15.5107 will cause this problem on HMIBMU.
To fix the issue you have to apply the ver. 15.40.48.5171 .
Intel® Graphics Driver for Windows:
https://downloadcenter.intel.com/download/30196/Intel-Graphics-Driver-for-Windows-15-40-
Impacted products SN:
SES-BM2332-H842AE TBN1213088
TBN1213089
TBN1213090
TBN1213091
TBN1213092
TBN1213093
TBN1214355
TBN1214356
TBN1214357
TBN1214358
TBN1214359
TBN1214360
SES-BM2332-S842AE TBNB202413
TBNB202414
TBNB202415
TBNB202416
TBNB202417
TBNB202418
TBNA202251
TBNA202252
TBNA202253
TBNA202254
TBNA202255
TBNA202256
TBN1214362
TBN1214363
TBN1214364
TBN1214365
TBN1214366
TBNB203897
TBNB203898
TBNB203899
TBNB203900
TBNB203901
TBNB203902
TBN1211459
TBN1211460
TBN1211461
TBN1211462
TBN1211463
TBN1211464
SES-BM2334-H84MAE TBNB201684
TBNB201685
TBNB201686
TBNB201687
TBNB201688
TBNB201689
SES-BM2334-S84MAE TBN1213372
TBN1213373
TBN1213374
TBN1213375
TBN1213376
TBN1213377
The article is applicable to HMIBMU*I29D*10*, HMIBMU*I29D*E0* Win 10 LTSC 1809
See below the serial numbers
Intel graphic driver 20.19.15.5107 will cause this problem on HMIBMU.
To fix the issue you have to apply the ver. 15.40.48.5171 .
Intel® Graphics Driver for Windows:
https://downloadcenter.intel.com/download/30196/Intel-Graphics-Driver-for-Windows-15-40-
Impacted products SN:
SES-BM2332-H842AE TBN1213088
TBN1213089
TBN1213090
TBN1213091
TBN1213092
TBN1213093
TBN1214355
TBN1214356
TBN1214357
TBN1214358
TBN1214359
TBN1214360
SES-BM2332-S842AE TBNB202413
TBNB202414
TBNB202415
TBNB202416
TBNB202417
TBNB202418
TBNA202251
TBNA202252
TBNA202253
TBNA202254
TBNA202255
TBNA202256
TBN1214362
TBN1214363
TBN1214364
TBN1214365
TBN1214366
TBNB203897
TBNB203898
TBNB203899
TBNB203900
TBNB203901
TBNB203902
TBN1211459
TBN1211460
TBN1211461
TBN1211462
TBN1211463
TBN1211464
SES-BM2334-H84MAE TBNB201684
TBNB201685
TBNB201686
TBNB201687
TBNB201688
TBNB201689
SES-BM2334-S84MAE TBN1213372
TBN1213373
TBN1213374
TBN1213375
TBN1213376
TBN1213377
Опубліковано для: Schneider Electric Україна