Чим ми можемо вам допомогти сьогодні?

Masterpact MTZ: Components needed to locally operate breaker via smartphone app

Issue: Local operation via phone app capability was not ordered from the factory.  Need to field modify.
Product Line: Circuit Breakers
Environment: Masterpact MTZ

Resolution: to field modify, the following components are required. Some of these parts may already be installed.

  • Mobile App – EcoStruxure Power Device
  • Masterpact Operation Assistant Digital Module LV850005
  • XF-Com, MX-Com coils, part numbers vary based on voltage.
  • Spring Charging Motor, part numbers vary based on voltage.
  • Isolation Module LV850056SP

Isolation module

  • Isolation Module to coils communication cables MTZ1: LV833118SP, MTZ2/MTZ3: LV847904SP

isolation module to coil cables

  • MX-Com cable needs to be plugged into the MX1 location on Isolation module, not MX2.

Isolation module MX1 wiring location

  • Coils properly wired, C3 and A3 continuously powered. C2 and A2 are only needed for push button operation.

coil wiring diagram

  • Accessories Declared in the Control Unit via EPC, click the accessory pencil

edit breaker accessories


Then declare accessories
declare accessories

Schneider Electric Україна

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings