Чим ми можемо вам допомогти сьогодні?

What does an OBF fault mean on an ATV12 drive?

Article available in these languages:

  • Spanish

Resolution:
The OBF (Over Braking Fault) occurs when the drive detects excessive braking energy, typically caused by rapid deceleration or high load inertia.

Possible causes are:

  • Deceleration time is too short
  • High inertia load (motor or driven machine)
  • Input line voltage too high
  • Voltage spikes or surges in the power supply

To mitigate the issues:

  • Increase the deceleration time (DEC) to reduce braking stress
  • Install a braking resistor or braking module if required
  • Verify the line supply voltage is within limits- Must not exceed +20% of the rated voltage during operation
  • Check for voltage fluctuations, spikes, or unstable power conditions

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings