Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
"S_RD_ETH_MX2" is not working as expected
The issue is fixed in Control Expert version 15.1

The following information explains what was fixed to resolve the issue.

The fix for the issue involved two corrections:
  • The diagnostic parameter “NEW” which was not working as explained in the documentation.
  • One very specific use case was taken into account where the DFB S_RD_ETH_MX2 could update data into OUTPUT_SAFE_DATA with some data older than the one which was already existing (but still compliant with the SAFETY_CONTROL_TIMEOUT). However, these conditions could not appear in a normal condition system and could be revealed only by very specific conditions (insertion of corrupted and very specific time data)




Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:

Потрібна допомога?

  • Інструмент вибору продукту

    Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.

  • Розрахувати вартість

    Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець

  • Де придбати?

    Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

  • Довідковий центр

    Знайдіть усі необхідні ресурси для підтримки в одному місці.

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміна продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • Ecostruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings