How to set up an ATV212 for dual ramp functionality?
Under main menu,
ACC and DEC will be the first set of ramp up and down times.
Set AU1 to 0 to disable auto ramp feature.
Under AUF, F---:
Set F500 (acc2) for second ramp up time based on frequency threshold (F505).
Set F501 (Dec2) for second ramp down time.
Ramp switching can also be accomplished based on a logic input trigger vs a hz value threshold.
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)“
Опубліковано для: Schneider Electric Україна



