Why my M580 CPU is no more accessible from "Control Expert" software using USB and Ethernet links?
If the CPU detects a "duplicate IP address", that means that, in your application program, the Ethernet IP address of the CPU is equal to the IP address of the USB: 90.0.0.1 or 90.0.0.2
The table below, shows in yellow text highlight, the signature of a duplicate address.
An example of configuration that generates a duplicate address
At the end of the transfer, the CPU configures its Ethernet port in 90.0.0.1 and 90.0.0.2, so the CPU creates a duplicate IP address with its USB port (90.0.0.1.
How to proceed to reset the configuration?
Move the CPU to slot n°2 of the rack and power on the PLC. => The CPU will move in "no-conf".
You'll have then the possibility to transfer in the CPU a more conventional configuration.