How do I upgrade the firmware of the BMENUA0100 OPCUA server module?

First log into the module via the web pages and go to the cyber security setup tab then select access control

image1

Create an account and select the appropriate roles for the user, "installer" necessary

image2

Apply the changes

image3

Launch the Automation Device Maintenance utility and select settings then package settings. The package location is where you copy the firmware file to

image5

The firmware should be available in the list under the data package

image6

Next, select Device/Loading tab and select Add

image7

Set the connection to HTTP/HTTPS and enter the IP address of the BMENUA0100 module then select ok

image8

Device should appear in the device list, make sure the data package reflect the firmware version you are upgrading to. Then select "Device Login" icon and enter the user credential of the module and select "connect"

image8b

The device login icon should turn green indicating a valid login. Next select the "Update Firmware" button at the bottom

image9

Schneider Electric Україна

Досліджуйте більше
Продукт:
Досліджуйте більше
Продукт:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings