Using Pick Action For "Change Main Server" Action
This Pick Action can be used to switch between servers for users in ViewX with restricted database access. Administrators may need a simple and secure way to switch between servers—especially during or after a failover event. The Pick Action feature provides a streamlined solution for this scenario. With a single button click, the Pick Action presents a list of available servers. Users can then select the desired server from the list, enabling quick and controlled server switching without requiring elevated database permissions
- Create a new mimic and create a button from the Graphical tab in ViewX.
- Double click the button to display “Button Properties” dialog.
- Click the “Pick Action” button.
- From the Pick action configuration, select “Method” and click “Next”
- Click the ellipsis on the right and locate root explorer.
- Beside “Method” select from the drop-down list “Change Main Server” and click “Next”.
- Click “Next” button twice and “Finish”.
- Save changes and place in “Run Mode”.
Опубліковано для: Schneider Electric Україна
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.