How do I update the firmware of my SRTG 15 & 20kVA UPS?
Issue:
SRTG 15 & 20kVA UPS requires a firmware update.
Product Line:
Smart-UPS models SRTG15KXLI and SRTG20KXLI
Environment:
- Computer with Windows 7 or Windows 10 operating system
- The USB A to USB B type communication cable supplied with the UPS
- "UPS-UpdateToolInstaller.zip" file - available at the end of this document
- "15-20k V1.19 20220909.zip" Firmware File - available at the end of this document
Resolution:
NOTE: The UPS system is expected to power down during the firmware upgrade. It is recommended to turn off the load connected to the UPS before starting the firmware upgrade.
Preparation:
- Connect the USB A to USB B type communication cable supplied with the UPS cable between the UPS and computer.
- Download the "UPS-UpdateToolInstaller.zip" and "15-20k V1.19 20220909.zip" files attached at the end of this document.
- Extract the "UPS-UpdateToolInstaller.zip" file.
Installing the Update Tool:
Double click the "UPS-UpdateToolInstaller.exe" file to start installing the update tool.
- Select OK.
- Select Next.
- Select Install.
- Ensure that the "Launch UPS-UpdateTool" option is selected, and then select Finish. This will launch the update tool.
Updating the UPS Firmware:
- Select the language: English.
- Select the appropriate port number where the USB cable is connected to the computer.
- Press "select" and browse to the location where the "15-20k V1.19 20220909.zip" file was downloaded in Preparation Step 2.
- Ensure both check boxes are ticked:
- Select Updating:
- The update may take 15-20 minutes. Once the update is completed, the update tool can be closed:
Verifying the firmware version
Use the UPS front panel to navigate to the following menus.
- Press the OK key to enter the Main Menu, press the ▼ key to select Configuration and press the OK key to enter the submenu.
- Press the ▼ key to select Display, and click OK to enter the submenu.
- Press the ▼ key to select the Menu Type, and click OK to enter the menu type selection screen.
- Press ▼ key to select Advanced, and press OK to confirm.
- Press ESC key until you return to the Main Menu.
- In the Main Menu, press the ▼ key to select About, click OK to enter the submenu.
- Select UPS and click OK to enter the submenu.
-
-
- Press the ▼ key to view firmware component versions.
-
-
Опубліковано для: Schneider Electric Україна




Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.