Чим ми можемо вам допомогти сьогодні?

PowerChute Serial Shutdown does not report a self-test has run when connected to a Back-UPS.

Issue:
PowerChute Serial Shutdown does not report when a self-test has been run when connected to a Back-UPS if a user presses and holds the Back-UPS's power on button to trigger a self-test. Also, a Back-UPS will run a self-test every 14 days from the date/time of the last self-test. When the UPS triggers the scheduled self-test, PowerChute will not record that the test has been run.

NOTE: If you initiate a UPS self-test via the PowerChute UI diagnostics page for Back-UPS models, the result may return as “Unknown.” If this occurs, then try initiating the self-test again. If the issue persists, your Back-UPS may not support manual self-tests. See Schneider Electric FAQ000266376 Self-test fails on Back-UPS when the test is run from PowerChute Serial Shutdown

Products:
PowerChute Serial Shutdown
Back-UPS

Environment:
PowerChute Serial Shutdown connected to a Back-UPS.

Cause:
A mistranslation of the event by PowerChute.

Solution:
This issue will be resolved in a future release.

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings