Issue
When trying to connect to an M221 using Machine Expert Basic using a USB cable I get a "Cannot launch ModbusDrv.exe" error message and I'm not able to connect.
Product Line
Machine Expert Basic, M221
Environment
Machine Expert Basic
Cause
There is an issue with the M221 driver
Resolution
To resolve this issue, the driver needs to be reinstalled. Steps to reinstall it:
1/ Go to: "C:\Program Files (x86)\Common Files\Schneider Electric Shared\M221"
By default the driver is installed on this location after EME Basic is installed.
2/ Right-click on the M211_Controller.inf file and select Install.
3/Try connecting to the M221 again.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.